SYMAP® - Types Y, X, BC: EC, ECG, F, G, M, T, LD, X, XG, BC, BCG
|
Hardware capabilities of SYMAP® family
◊ optional ♦ standard
— not available
|
| SYMAP® | Y Type | X Type | BC Type | EC | ECG | F | G | M | T | LD | X | XG | BC | BCG | | Front panel | | | Graphic-LCD | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| Keyboard | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 7 segment displays | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 8 Alarm LEDs | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| Transponder access | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| COMMUNICATION | | | RS232 | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| PROFIBUS | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ |
| MODBUS | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ |
| CANBUS1 | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | — | ◊ | ◊ | ◊ | ◊ |
| CANBUS2 | ◊ | ◊ | — | — | — | — | — | ◊ | ◊ | ◊ | ◊ |
| RS485/RS422 | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ |
| IEC 60870-5-103, RS485 | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ |
| MODEM (analog) | ◊ | ◊ | — | — | — | — | — | — | — | — | — |
| MODEM (ISDN) | ◊ | ◊ | — | — | — | — | — | — | — | — | — |
| IEC 61850 | — | — | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | — | ◊ | — |
| INPUTS/OUTPUTS | | | Digital inputs | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 14 | 14 | 14 | 14 |
| Digital inputs ext. board | — | — | — | — | — | — | — | (36) | (36) | (36) | (36) |
| Relay outputs basic unit | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 12 | 12 | 12 | 12 |
| Relay outputs ext. board | — | — | — | — | — | — | — | (24) | (24) | (24) | (24) |
| ANALOG I/O 4-20 mA | | | Analog in 4-20 mA | (2) | (2) | (2) | (2) | (2) | (2) | — | 4 | 4 | 4 | 4 |
| Analog out 4-20 mA | (2) | (2) | (2) | (2) | (2) | (2) | — | 4 | 4 | 4 | 4 |
| PT100/PT1000 + ext. converter | — | — | — | — | (8) | — | — | (4) | (4) | (4) | (4) |
| PT100/PT1000 ext. board | — | — | — | — | — | — | — | (21) | (21) | (21) | (21) |
| ANALOG INPUT FOR MEASURING AND PROTECTION | | | Total analog inputs | 9 | 9 | 13 | 13 | 13 | 13 | 13 | 13 | 13 | 17 | 17 |
| 3 CT’s for FEEDER CURRENT | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 3 Ph.current via combined sensor | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 3 CT’s for DIFF. CURRENT | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| CT for GROUND CURRENT 1 | — | ♦ | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦ | ♦ |
| CT for GROUND CURRENT 2 | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 3 PT&rsquos for FEEDER VOLTAGE | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 3 Ph.voltage via combined sensor | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 3 PT’s for BUS VOLTAGE 1 | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ◊ |
| 3 PT’s for BUS VOLTAGE 2 | — | ◊ | — | — | — | — | — | ◊ | ◊ | ◊ | ◊ |
| PT for GROUND VOLTAGE 1 | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦* | ♦ | ♦ |
| PT for GROUND VOLTAGE 2 | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| RECORDING UNIT | | | Data logger | — | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ | ◊ |
| Detailed protection history | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
|
Software capabilities of SYMAP® family
◊ optional ♦ standard
— not available
|
| SYMAP® | Y Type | X Type | BC Type | EC | ECG | F | G | M | T | LD | X | XG | BC | BCG | | POWER MANAGEMENT MODULES | | | Synchronizing unit | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| Load sharing/asymmetrical load ctrl. | — | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Frequency controller | ◊ | ♦ | — | — | — | — | — | — | ♦ | — | ♦ |
| Voltage regulator | ♦ | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Power factor control | — | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Load controller (big consumer) | — | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Load depending start/stop (PMS) | — | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Preferential trip management | — | ◊ | — | — | — | — | — | — | ♦ | — | ♦ |
| Blackout management | ♦ | ♦ | — | — | — | — | — | — | ♦ | — | ♦ |
| Diesel control | ♦ | ♦ | — | — | — | — | — | — | ♦ | — | ♦ |
| LOGIC BUILDER UNIT (PLC) | | | Breaker controls/interlocks | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| Logic diagrams | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| PROTECTION RELAYS (ACCORDING TO ANSI DEVICE NUMBER | | | 15 | - Matching device (motorpoti) | ♦ | ♦ | — | — | — | — | — | ♦ | ♦ | ♦ | ♦ |
| 24 | - Overexcitation protection | — | ♦ | — | ♦ | ♦ | — | — | ♦ | ♦ | ♦ | ♦ |
| 25/A | - Automatic synchronizing | ♦ | ♦ | ♦ | ♦ | ♦ | — | — | ♦ | ♦ | ♦ | ♦ |
| 27 | - Undervoltage, inst., def. time | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 27B | - BUS undervoltage, def.time | ♦ | ♦ | ♦ | — | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 32 | - Overload relay | — | ♦ | ♦ | ♦ | ♦ | ♦ | — | ♦ | ♦ | ♦ | ♦ |
| 37 | - Undercurrent protection | — | ♦ | — | ♦ | ♦ | ♦ | — | ♦ | ♦ | ♦ | ♦ |
| 40/Q | - Loss of field, reac.power, impedance | — | ♦ | — | — | — | — | — | ♦ | ♦ | ♦ | ♦ |
| 46 | - Reverse phase current | — | ♦ | — | ♦ | ♦ | — | — | ♦ | ♦ | ♦ | ♦ |
| 47 | - Phase sequence voltage | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 49 | - Thermal overload protection | — | ♦ | ♦ | ♦ | ♦ | ♦ | — | ♦ | ♦ | ♦ | ♦ |
| 50BF | - Breaker failure | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 50 | - Overcurrent, instantaneous | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 50G/N | - Current earth fault, instantaneous | — | ◊ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 51 | - AC time overcurrent, def.time, IDMT | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 51G/N | - AC Ground overcurr., def.time, IDMT | — | ◊ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 51LR | - Locked rotor | — | — | — | — | ♦ | — | — | ♦ | ♦ | ♦ | ♦ |
| 51V | - Voltage restrained overcurrent | — | — | — | — | ♦ | — | — | ♦ | ♦ | ♦ | ♦ |
| 59 | - Overvoltage, inst., def. time, norm.inv. | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 59B | - BUS overvoltage, relay definite time | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 59N | - Residual overvoltage | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 64 | - Ground overvoltage | ♦ | ◊ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 66 | - Start inhibit | ♦ | — | — | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 67 | - AC dir. overcurrent, def. time, IDMT | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 67GS/GD | - AC directional earth fault, definite time | — | ◊ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 78 | - Vector surge supervision | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 78S | - Out of step tripping | — | — | — | ♦ | — | — | — | ♦ | ♦ | ♦ | ♦ |
| 79 | - Auto reclosing | — | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 81 | - Frequency supervision | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 81B | - BUS frequency supervision | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 86 | - Electrical lock out | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 87G/M | - Generator/Motor differential | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 87LD | - Line differential | — | — | — | — | — | — | ♦ | — | — | — | — |
| 87N | - Restrict earth fault relay | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 87T | - Transformer differential | — | — | — | — | — | — | — | — | — | ♦ | ♦ |
| 94 | - Trip circuit supervision | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| 95i | - Inrush blocking | — | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| -- FF | - Fuse failure (voltages) | — | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ |
| -- FL | - Fault locator | — | — | ♦ | — | — | — | — | ♦ | — | ♦ | — |
|
|
|